Description
Product Details:
Category:Vacuum Circuit Breaker
Name:Indoor high voltage circuit breaker
Model:ZN12-12
Packing:Plastic bag & Wooden case or as requested
Delivery & Payment Terms:
Shipping time: Usually 30 days after the ordered confirmed
Payment:T/T, L/C, Western Union or Paypal
Trade term:FOB China port, or CIF
Environment Condition:
– Ambient temperature:-25℃~+40℃
– Altitude: ≤1000m
– Daily average relative humidity: ≤95%; Monthly average relative humidity: ≤90%
– Daily average saturated vapor pressure: ≤2.2KPa; Monthly average value : ≤1.8KPa
– Earthquake intensity: ≤8 degree
– No fire, explosion, severe vibration, chemical corrosion and serious pollution
Technical Data
1 | Rated voltage | KV | 12, 40.5 | ||
2 | Rated lighting impulse withstand voltage | KV | Phase to phase or to Ground 75, fracture 80 | ||
3 | Rated short-time power frequency withstand voltage | KV | Phase to phase or to Ground 42, fracture 48 | ||
4 | Rated short-circuit breaking current | KA | 20, 25 | 31.5 | 40 |
5 | Rated current | A | 630/1250/1600 | 1250/1600/2000/2500 | 1600/2000/3150 |
6 | Rated thermo stability current(valid) | KA | 25 | 31.5 | 40 |
7 | Rated dynamic stability current(peak) | KA | 63 | 80 | 100 |
8 | Rated short-circuit making current(peak) | KA | 63 | 80 | 100 |
9 | Rated operations of short-circuit breaking current interruption | Times | 50(40kA is 30) | ||
10 | Rated working current of over current and tripping coil | A | 5 | ||
11 | Rated operating sequence | 0-0.3s-CO-180s -CO/0-180s-CO-180s-CO(40KA) | |||
12 | Rated current of auxiliary switch | A | AC10,DC5 | ||
13 | Rated voltage of energy saving release | V | AC.DC220 AC.DC110 | ||
14 | Closing time | Times | ≤75 | ||
15 | Opening time | ≤60(40) | |||
16 | Power of energy saving motor | W | 275 | ||
17 | Energy saving time | S | ≤15 | ||
18 | Mechanical life | Times | 20000 |
Mechanical characteristics adjustment data
1 | Rated contact stroke | mm | 11 ±1 | ||
2 | Contact over travel | mm | 8±2 | ||
3 | Average opening speed | m/s | 1.0~1.8 | ||
4 | Average closing speed | m/s | 0.6~1.1 | 0.8~1.3 | 0.8~1.3 |
5 | Contact bouncing duration at closing operation | ms | ≤2 | ||
6 | Core distance between phases | mm | 210,230,250,275,280 | ||
7 | Three-pole simultaneity | ms | ≤2 | ||
8 | Conductive circuit resistance of each phases | μΩ | <40 |
Outline Dimension
Product Inquiry