Description
Product Details:
Category:High Voltage Disconnecting Switch
Name:Indoor Isolating switch, Disconnector, Isolator
Model:GW8(GW13)-40.5,72.5, 126
Packing:Plastic bag & Wooden case or as requested
Delivery & Payment Terms:
Shipping time: Usually 21 days after the ordered confirmed
Payment:T/T, L/C, Western Union or Paypal
Trade term:FOB China port, or CIF
Environment condition
– Ambient temperature: max +40°C min -25°C
– Altitude: ≤1000m
– Wind pressure: ≤700Pa (equals to wind speed 34m/s)
– Air contamination degree: Ⅲ degree
– Earthquake intensity: ≤8 degree
– No corrosive or flammable gas, no frequent violent vibration
Technical Data
Model | GW8 | GW13 | ||||||
1 | Rated Voltage (kV) | 40.5 | 72.5 | 126 | 40.5 | 72.5 | 126 | |
2 | 1min power frequency withstand voltage (kV) | 85 | 140 | 230 | 85 | 160 | 230 | |
3 | Lightning impulse withstand voltage (kV) | 185 | 325 | 550 | 185 | 350 | 550 | |
4 | Rated Current (A) | 630 | 630, 1250, 1600 | |||||
5 | Rated short time withstand Current (kA/S) | 25/4 | 40/4 | |||||
6 | Rated peak withstand current kA) | 63 | 100 | |||||
7 | Rated connect machine load (N) | 750 | 750 | 1000 | 750 | 100 | 1250 | |
8 | Mechanical life (Times) | 2000 | 2000 | |||||
9 | Electromotor operation mechanism | Model | CJ2 | CJ2 | ||||
Motor voltage (V) | AC380, DC220, DC110 | AC380, DC220, DC110 | ||||||
Control loop voltage (V) | AC220, AC380, DC220, DC110 | AC220, AC380, DC220, DC110 | ||||||
Switching time (s) | 7±1 | 7±1 | ||||||
Output corner | 180° | 180° | ||||||
10 | Manual operation mechanism | Model | CS14G | CS14G | ||||
Control loop voltage (V) | AC220 | AC220 |
Outline Dimension
1. Terminal block 2. Rain cover 3. Touch guide base 4. Moving contact conducting rod
5. Upper insulating Pillar 6. Bracket 7. Lower insulating Pillar 8. Chassis
Product Inquiry